View and Download Edwards Signaling 2412 installation instructions & owner's operation manual online. 2400 Series Fire Alarm Control Panels. 2412 Control Panel pdf manual download.
Home> Industries & Applications> Commercial Facilities> Fire Alarm Products
E-FSA250
Edwards Signaling Fire Alarm Control Panel Operating Instructions For models: E-FSA64G, E-FSA64GD, E-FSA64R, E-FSA64RD, E-FSA250G, E-FSA250GD, E-FSA250R, E-FSA250RD For additional information, refer to the Edwards Signaling eFSA64 and eFSA250 Technical Reference Manual (P/N 3101202-EN). Get Edwards Signaling 5531MHV Instruction Manual. Get all Edwards Signaling manuals! Edwards Signaling Manuals. Or point us to the URL where the manual is.
254-Point Analog/Addressable Life Safety System
Description
Note: The E-FSA250 has been replaced by the FX-1000 intelligent addressable panel. The Edwards Signaling E-FSA250 life safety system offers the reliability of analog/addressable fire detection for small to mid-sized applications. Built to provide years of trouble-free service, this system benefits building owners and installers with rotory device addressing, optional Ethernet® connectivity, and a full line of easy-to-configure option cards and modules. The E-FSA250 provides one Class A or Class B analog/addressable device loop that supports up to 127 devices. A second 127-point loop may be added to the E-FSA250 to expand total system capacity to up to 254 device addresses. The panel includes four NACs that may be wired for either Class A or Class B operation. The E-FSA250 supports a wide range of accessories and related equipment, including:
| Link to this product for email: For web page (with image): |
Catalog Numbers
Catalog Number | Description |
Specifications
![Edwards Signaling Fsa Fire Panel User Manual Edwards Signaling Fsa Fire Panel User Manual](/uploads/1/3/3/9/133918008/866911368.jpg)
Approvals
Agency ApprovalsEdwards Signaling Fsa Fire Panel User Manual Instructions
Specifications- Device loops: 1 loop, expandable to 2, Class A or B, each loop supporting up to 127 device addresses
- NAC Circuits: 4 Class B or 2 Class A, 2.5 amps each
- Power supply 6.0A total, 2.5A max. per circuit at 120/230V AC 60 Hz; 5.0A total at 230V AC 50Hz, 2.5A max. per circuit; 0.5 amps aux. power
- NAC Operating Voltage: 24V DC. NAC minimum voltage: 19.5V DC @ 20.4V battery voltage
- Loop circuit operating voltage: 20V peak-to-peak
- Primary power: 120V AC 60 Hz, 230V AC 50 - 60 Hz
- Aux Power 1 (Continuous Circuit): 24V DC nominal at 500 mA
- Aux Power 2 (Resettable circuit): 24V DC nominal at 500 mA
- Auxiliary output: 19 to 25.7V DC
- Base panel current: Standby - 172 mA, Alarm - 267 mA
- Battery placement: E-FSA250 cabinets accommodate up to 18AH batteries. Use an external cabinet for larger sizes
- Batteries: Batteries must be sealed lead acid type only. Maximum charging capacity = 26AH
- Loop circuit: Maximum loop resistance: 66 ohms. Maximum loop capacitance: 0.5 microF. Style 4, 6, and 7 wiring. 64 isolators maximum.
- Compatibility ID: 100
- Alarm contact: Form C 24V DC @ 1A (resistive load)
- Trouble contact: Form C 24V DC @ 1A (resistive load)
- Supervisory contact: Form A 24V DC @ 1A (resistive load)
- Environmental: Temperature: 0 to 49C (32 to 120F). Humidity: 0 to 93% RH, noncondensing
- Terminal Rating: All terminals rated for 12 to 18 AWG (0.75 - 2.5 mm2
- Serial communications: Voltage: 2.55V. Current: 30 mA max
- Remote annunciator: 8 drops max, RS485 Class A or B
- Input zones: 32 max.
Documentation
Brochures- Fire Alarm Life Safety Product Guide.pdfA guide for the Edwards fire alarm products, including the E-FSC conventional panels, E-FSA addressable panels, initiating devices, signaling devices, and accessories.
- Fire Alarm FAQs_v2.pdfThis contains a list of commonly asked questions (with answers) regarding fire alarm systems.
- NAC Load_Wiring and dB_Calcs_V8.xlsThis spreadsheet will help calculate signal circuit loads, wire distances, and dB loss for speaker circuits.
- Addressable Fire Alarm System Questions to AskQuestions to ask to help put together a bill of material for an addressable fire alarm system.
- 85001-0541-E--Strobe Handbook.pdfA guide to the application and installation of fire alarm strobe devices.
- E-FSA Panel Battery CalculationsBattery calculations for the E-FSA addressable fire alarm panels.
- Firmware Update UtilityThis utility program is used to update the panel firmware in the E-FSA addressable panels. It works with panel firmware versions 2.2 and higher. The panel firmware itself is separate.
- E-FSA Firmware, Version 2.31.This is version 2.31 of the E-FSA addressable panel firmware. Copy to your hard drive, then uzip.
- Panel Firmware to CU Cross ReferenceThis lists what versions of the FSA-CU works with the different versions of panel firmware.
- Firmware Update Utility InstructionsThese are the instructions for using the Firmware Update Utility (FUU) used with the E-FSA addressable panels. Additional instructions can be found in the Help menu of the FUU.
- FSA-CU Programming Guide_v3.pdfA guide to using the FSA-CU configuration utility program with the E-FSA addressable fire alarm panels.
- FSA-CU v3.5_Setup.zipConfiguration utility program for the E-FS, E-FSC, and E-FSA fire alarm panels. Copy the file to your hard drive, unzip it, then click on the FSA-CU_Setup application to install.
- TF-13029.zipUtility for identifing possible nuisance conditions with E-PD and E-PHD addressable detectors. For an explanation of the issue and instructions for the utility, refer to Field Notes Bulletin 13029E in the Technical Bulletins section.
- AE Bulletin_E-FSA Strobe Synchronizaton.pdfInformation on how to configure signal circuits on the E-FSA panel to synchronize Edwards' Genesis strobes.
- AE Bulletin 050610-2_Booster Supply and E-FSA.pdfTips on how to wire a booster power supply to the E-FSA panels.
- Field Notes Bulletin_13029E_E-FSA Possible Nuisance Conditions With E-PD and E-PHD Detectors.pdfBulletin describing possible nuisance conditions with the E-PD and E-PHD addressable detectors and instructions for using the TF-13029 utility.
- AE Bulletin 100913_Laptop Connection Update.pdfTips on how to connect a laptop running the FSA-CU configuation utility program to an E-FSA addressable panel.
- AE Bulletin, E-FSA Panel Modem ConnectionsTips on connecting to an E-FSA addressable panel via modem.
- AE Bulletin, E-FSA Panel Cross ZoningTips on how to do cross zoning with the E-FSA addressable panels.
- AE Bulletin_E-FSA_Loop_Wiring_Ed.pdfWiring distances/limitations for the E-FSA addressable loop.
- AE Bulletin_FSA-CU_Getting_Started_Ed.pdfTips on using the FSA-CU configuration utility program for the E-FSA panel.
- AE Bulletin_E-FSA_RS232_Connection_Troubleshooting_Ed.pdfTips on connecting a laptop to the E-FSA panel for programming.
- AE Bulletin_RS232_DB9_Connection_Diagram_Ed.pdfRS232 cable connection diagram for connecting a laptop to the E-FSA panels.
- AE Bulletin_E-FSA_Loop_Faults.pdfTrouble shooting tips for loop faults on the E-FSA panels.
- AE_Bull_011513_Dialers_Internet_Cell.pdfThis bulletin provides tips for using Edwards dialers with TCP/IP internet and GSM (cellular phone) interface devices used for connecting to central monitoring stations.
- AE Bulletin_Elevator Recall & E-FSA_Update.pdfTips on how to program the E-FSA addressable panel for elevator control.
- Technical Bulletin - SA-DACT and Shared Phone LinesTechnical bulletin describing an issues with the SA-DACT dialer and shared phone lines.
- Technical Bulletin 16001E_R01_E-FSA Addressable Panels - Device Internal Fault Restoration IssueThis is a technical bulletin regarding internal device faults with E-FSA addressable panels. Bulletin explains issue and how to resolve.
- Product_Bulletin 052316 E-PDD Replacement EdwardsThis bulletin announces the replacement for the E-PDD addressable duct detector.
- AE Bulletin, E-FSA Panel & Latched OutputsTips on how to use and program latching outputs on an E-FSA addressable panel.
- Sounder Base ProgrammingTips on how to program (turn on) the addressable SB4U sounder base.
- Tech Bulletin, (ERROR) 5003 NAC AAn explanation of a an FSA-CU error message and how to resolve.
- AE Bulletin, Door Holders and Fire AlarmTips on how to connect door holders to fire alarm systems.
- AE Bulletin 091311_Sounder Base Wiring.pdfTips on how to wire and supervise the power to SB4U addressable sounder bases.
- Tech Bulletin 090811-2 Dialer Troubleshooting.pdfTips on troubleshooting problems with dialers.
- Tech Bulletin, Smoke Supervisory Configuration FaultAn explanation of a configuration fault caused by programming a smoke detector as a supervisory input using the FSA-CU, and how to resolve.
- Tech Bulletin, E-FSA NAC Device TypeAn explanation of how to properly configure the NACs in the E-FSA panels.
- Tech Bulletin, E-FSA Smoke Det, Sup Non-LatchDescribes an issue regarding using v3.3 of the FSA-CU to program a smoke detector as a supervisory non-latch device type.
- E-FSA Panel Firmware and FSA-CU Cross ReferenceA cross reference list that shows what E-FSA panel firmware works with which version of the FSA-CU programming software.
Advertising
Programming
3.10
FireShield Technical Reference Manual
Tip:
Don’t forget that you can press Reset or Signal Silence &
![Edwards fire panel Edwards fire panel](/uploads/1/3/3/9/133918008/568933855.jpg)
Drill to scroll through the list of settings. It may be faster to
press Signal Silence & Drill to scroll backwards through the
settings.
press Signal Silence & Drill to scroll backwards through the
settings.
To enter the current date:
1. Press Reset until the correct month is displayed.
2. Press Panel Silence to save the month setting and advance
to the day setting.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the correct day is displayed.
4. Press Panel Silence to save the day setting and advance to
the year setting.
The trouble buzzer sounds a long beep as confirmation.
5. Press Reset until the correct year is displayed.
6. Press Panel Silence to save the year setting and advance
to the next option.
Interye home care assessment form and users manual. The trouble buzzer sounds a long beep as confirmation.
5. Enter the time
Description: Sets the current time.
Format: HHMM
Default: 0000
To enter the current time:
1. Press Reset until the correct hour is displayed.
2. Press Panel Silence to save the hour setting and advance
to the minute setting.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the correct minute is displayed.
4. Press Panel Silence to save the minute setting and
advance to the next program option.
The trouble buzzer sounds a long beep as confirmation.
6. Select the FSDACT mode
Description: Determines how the FSDACT operates.
Settings: Single Line DACT
Dual Line DACT (required by UL 864)
Modem/LCD
only
LCD
only
Default: Dual Line DACT
To select the desired FSDACT mode:
1. Press Reset to select the desired format.
2. Press Panel Silence to save and advance to the next step.
Edwards Signaling Fsa Fire Panel User Manual Pdf
The trouble buzzer sounds a long beep as confirmation.
Note:
If Single Line DACT is selected, dual line programming
is skipped. If Modem/LCD only is selected, all account and
receiver related programming is skipped. If LCD only is
selected, all account, receiver, and telephone related
programming is skipped.
receiver related programming is skipped. If LCD only is
selected, all account, receiver, and telephone related
programming is skipped.
7. Enter the (DACR1) primary phone number
If a DACR1 primary phone number is not entered, skip
“Enter the (DACR1) secondary phone number” through
“Enter retry count one,” inclusive.
“Enter retry count one,” inclusive.
Edwards Signaling Fsa Fire Panel User Manual 2016
Description: Specifies the primary phone number that is used
to contact the central monitoring station.
to contact the central monitoring station.
Format: Up to 20 digits
Default: Blank
Tip:
If you save an incorrect digit, press Walk Test then
Remote Disconnect. This returns the cursor to the first digit.
Press Panel Silence until the cursor is at the incorrect digit.
Enter the correct digit, then press Panel Silence to save and
advance to the next digit.
Press Panel Silence until the cursor is at the incorrect digit.
Enter the correct digit, then press Panel Silence to save and
advance to the next digit.
Edwards Signaling Fsa Fire Panel User Manual 2017
To enter the primary phone number:
1. Press Reset until the first digit of the phone number is
Perl manual pdf download. displayed.
2. Press Panel Silence to save and advance to the next digit.
The trouble buzzer sounds a long beep as confirmation.
3. Press Reset until the next digit is displayed.
4. Press Panel Silence to save and advance to the next digit.
5. Repeat steps 3 and 4 until all digits are entered.
Note:
If less than 20 digits are entered, press Panel
Silence again or Remote Disconnect to advance to the
next program option.
next program option.
6. When you press Panel Silence at the last digit (20th digit),
the system automatically advances you to the next
program option.
program option.
8. Enter the (DACR1) secondary phone number
Description: Specifies the secondary phone number that is
used to contact the central monitoring station.
used to contact the central monitoring station.
Format: Up to 20 digits
Default: Blank
To enter the secondary phone number, follow the same steps
you used to enter the primary phone number. (See “Enter the
(DACR1) primary phone number” above.)
you used to enter the primary phone number. (See “Enter the
(DACR1) primary phone number” above.)